Instrumentation Cables 

   EN 50288-7 Instrumentation Cables

XlPe Insulated, lsZH sheathed & overall screened Instrumentation cables (Multipair)

re-2X(st)H 90°c / 300V

EN 50288-7 Instrumentation Cables

STANDARDS

Basic design to EN 50288-7

Applications

The unarmoured LSZH sheathed cables are generally use for indoor installation and suitable for wet and damp areas. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the LSZH sheath can reduce toxic smoke and fume emission.

FIRE PERFORMANCE

Flame Retardance (Single Vertical
Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE
0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation
(Vertically-mounted bundled wires
& cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance** ICEA S-73-532

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min
60% of tensile strength/min.60% of elongation, *** denotes optional
.

VOLTAGE RATING

300V

CABLE CONSTRUCTION

Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.
Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
Binder tape: PETP transparent tape
Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

COLOUR CODE

Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.
Outer Sheath: Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES

Temperature Range During Operation (Fixed State): -30°C – +90°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius: 7.5 X Overall Diameter

CONSTRUCTION PARAMETERS

Caledonian Cable Code RE-2X(St)H
No. of Pairs
x2xCross Section
Nominal
Insulation
Thickness
Nominal
Outer Sheath
Thickness
Nominal
Overall
Diameter
Approx. 
Weight
No.x2xmm2 mm mm mm kg/km
0.5mm2, Multipair
RE-2X(St)H 2P0.5 2x2x0.5 0.35 0.9 7.6 66
RE-2X(St)H 4P0.5 4x2x0.5 0.35 0.9 8.8 98
RE-2X(St)H 5P0.5 5x2x0.5 0.35 1.0 9.8 112
RE-2X(St)H 6P0.5 6x2x0.5 0.35 1.0 10.6 133
RE-2X(St)H 8P0.5 8x2x0.5 0.35 1.0 11.3 161
RE-2X(St)H 10P0.5 10x2x0.5 0.35 1.1 12.9 200
RE-2X(St)H 12P0.5 12x2x0.5 0.35 1.1 13.5 242
RE-2X(St)H 16P0.5 16x2x0.5 0.35 1.1 15.2 288
RE-2X(St)H 20P0.5 20x2x0.5 0.35 1.2 16.9 376
RE-2X(St)H 24P0.5 24x2x0.5 0.35 1.2 18.3 426
0.75mm2, Multipair
RE-2X(St)H 2P0.75 2x2x0.75 0.38 0.9 8.5 87
RE-2X(St)H 4P0.75 3x2x0.75 0.38 1.0 10.0 122
RE-2X(St)H 5P0.75 4x2x0.75 0.38 1.0 10.9 154
RE-2X(St)H 6P0.75 5x2x0.75 0.38 1.0 11.8 174
RE-2X(St)H 8P0.75 8x2x0.75 0.38 1.1 12.8 213
RE-2X(St)H 10P0.75 10x2x0.75 0.38 1.1 14.5 266
RE-2X(St)H 12P0.75 12x2x0.75 0.38 1.1 15.1 304
RE-2X(St)H 16P0.75 16x2x0.75 0.38 1.2 17.3 398
RE-2X(St)H 20P0.75 20x2x0.75 0.38 1.3 19.2 478
RE-2X(St)H 24P0.75 24x2x0.75 0.38 1.3 20.8 559
1.0mm2, Multipair
RE-2X(St)H 2P1.0 2x2x1.0 0.4 0.9 9.2 101
RE-2X(St)H 4P1.0 3x2x1.0 0.4 1.0 10.9 157
RE-2X(St)H 5P1.0 4x2x1.0 0.4 1.0 11.9 194
RE-2X(St)H 6P1.0 5x2x1.0 0.4 1.0 13.0 223
RE-2X(St)H 8P1.0 8x2x1.0 0.4 1.1 14.0 272
RE-2X(St)H 10P1.0 10x2x1.0 0.4 1.1 15.9 334
RE-2X(St)H 12P1.0 12x2x1.0 0.4 1.2 16.8 390
RE-2X(St)H 16P1.0 16x2x1.0 0.4 1.2 19.0 511
RE-2X(St)H 20P1.0 20x2x1.0 0.4 1.3 21.1 617
RE-2X(St)H 24P1.0 24x2x1.0 0.4 1.4 23.1 749
1.3mm2, Multipair
RE-2X(St)H 2P1.3 2x2x1.3 0.45 1.0 10.4 124
RE-2X(St)H 4P1.3 3x2x1.3 0.45 1.0 12.0 184
RE-2X(St)H 5P1.3 4x2x1.3 0.45 1.1 13.4 226
RE-2X(St)H 6P1.3 5x2x1.3 0.45 1.1 14.6 289
RE-2X(St)H 8P1.3 8x2x1.3 0.45 1.2 15.7 337
RE-2X(St)H 10P1.3 10x2x1.3 0.45 1.2 17.9 411
RE-2X(St)H 12P1.3 12x2x1.3 0.45 1.3 18.9 495
RE-2X(St)H 16P1.3 16x2x1.3 0.45 1.3 21.4 651
RE-2X(St)H 20P1.3 20x2x1.3 0.45 1.4 23.8 772
RE-2X(St)H 24P1.3 24x2x1.3 0.45 1.5 25.9 933
1.5mm2, Multipair
RE-2X(St)H 2P1.5 2x2x1.5 0.45 1.0 10.8 139*
RE-2X(St)H 4P1.5 3x2x1.5 0.45 1.1 12.7 214
RE-2X(St)H 5P1.5 4x2x1.5 0.45 1.1 14.0 259
RE-2X(St)H 6P1.5 5x2x1.5 0.45 1.2 15.2 305
RE-2X(St)H 8P1.5 8x2x1.5 0.45 1.2 16.4 385
RE-2X(St)H 10P1.5 10x2x1.5 0.45 1.3 18.8 460
RE-2X(St)H 12P1.5 12x2x1.5 0.45 1.3 19.7 558
RE-2X(St)H 16P1.5 16x2x1.5 0.45 1.4 22.5 725
RE-2X(St)H 20P1.5 20x2x1.5 0.45 1.5 25.0 881
RE-2X(St)H 24P1.5 24x2x1.5 0.45 1.5 27.1 147
Note : Other conductor sizes & core configurations are available upon request.

Electrical PROPERTIES

Conductor Area Size   mm 2   0.5  0.75   1.0   1.3 1.5  
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C)   Ω/km  36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz)  pF/m(Max.)  
≤ 4 pairs 90 90 90 102 102
all other pairs 75 75 75 85 85
Capacitance unbalance(1 kHz)  pF/500 m (Max.) 500 
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage  Core to Core  1500 
Core to Screen  1500